Monnit Modbus Gateway

Monnit · Serial Modbus Gateway · ALTA

Monnit Modbus Gateway
Manufacturer
Monnit
Product
Serial Modbus Gateway
Model
ALTA
Protocol
Modbus
Updated
2026-02-19
Driver ID
180

Notes

Gateway for connecting Monnit wireless devices

Connect:
ezeio D0 -> Gateway D- (green)
ezeio D1 -> Gateway D+ (orange)
ezeio +V -> Gateway V+ (red)
ezeio 0V -> Gateway GND (black)

Make sure gateway "SELECT" jumper is OFF.
Gateway factory defaults to 19200/N/8/1
Default address 95

Registers 8

#NameUnitDescription
1Gateway serialUnique serial number
2Devices (Active)Number of registered sensors active
3Devices (Configured)Number of registered sensors configured to operate through the gateway
4Operating channelWireless channel in use 0-25
5Uptimes
6Active
7Full reset
8Network reset