- Monnit Modbus Gateway

- Manufacturer
- Monnit
- Product
- Serial Modbus Gateway
- Model
- ALTA
- Protocol
- Modbus
- Package
- Sensors (SU2202)
- Updated
- 2026-02-19
- Driver ID
- 180
Notes
Gateway for connecting Monnit wireless devices Connect: ezeio D0 -> Gateway D- (green) ezeio D1 -> Gateway D+ (orange) ezeio +V -> Gateway V+ (red) ezeio 0V -> Gateway GND (black) Make sure gateway "SELECT" jumper is OFF. Gateway factory defaults to 19200/N/8/1 Default address 95
Registers 8
| # | Name | Unit | Description |
|---|---|---|---|
| 1 | Gateway serial | Unique serial number | |
| 2 | Devices (Active) | Number of registered sensors active | |
| 3 | Devices (Configured) | Number of registered sensors configured to operate through the gateway | |
| 4 | Operating channel | Wireless channel in use 0-25 | |
| 5 | Uptime | s | |
| 6 | Active | ||
| 7 | Full reset | ||
| 8 | Network reset |