- Drivers
- Driver catalog
- Eastron SDM120

- Manufacturer
- Eastron
- Product
- SDM120
- Protocol
- Modbus
- Package
- Meters (SU2201)
- Updated
- 2023-11-13
- Driver ID
- 210
Notes
Single phase electric energy meter Connect : Meter 8 (G) -> ezeio 0V/Gnd Meter 9 (B-) -> ezeio D0 Meter 10 (A+) -> ezeio D1 Note: Meter max speed is 9600 bps. Address must be set via Modbus, writing to FLOAT register 21.
Registers 13
| # | Name | Unit | Description |
|---|---|---|---|
| 1 | Voltage | V | |
| 2 | Current | A | |
| 3 | Active Power | kW | |
| 4 | Apparent power | kVA | |
| 5 | Reactive power | kVAr | |
| 6 | Power factor | ||
| 7 | Frequency | Hz | |
| 8 | Active energy import | kWh | |
| 9 | Active energy export | kWh | |
| 10 | Reactive energy import | kVArh | |
| 11 | Reactive energy export | kVArh | |
| 12 | Total active energy | kWh | |
| 13 | Total reactive energy | kVArh |