Skip to content
ezeioDocs
  1. Drivers
  2. Driver catalog
  3. Thermostat T32P

Thermostat T32P

JacksonSystems · T32P/Chameleon · T32P

Thermostat T32P
Manufacturer
JacksonSystems
Product
T32P/Chameleon
Model
T32P
Protocol
Modbus
Updated
2025-07-16
Driver ID
322

Notes

Wall thermostat

Driver assumes thermostat is set for 2-point day/night mode (DIP 6 off & DIP 8 on).

Optional expression determines day/night mode.

Thermostat firmware version 2.16 and higher.

Connect:
ezeio D0 -> T32P Coms B
ezeio D1 -> T32P Coms A
ezeio 0V -> T32P Coms T

Registers 11

#NameUnitDescription
1CallRelay closures
2Outside TempOptional external temp sensor (read only)
3Room TempInternal temp sensor (read only)
4SetpointCurrent set point (read only)
5FanFan mode
6ModeThermostat mode
7Day Cool Set TempCooling set point in day mode
8Day Heat Set TempHeating set point in day mode
9Night Cool Set TempCooling set point in night mode
10Night Heat Set TempHeating set point in night mode
11Day/Night modeSet day or night mode