- Drivers
- Driver catalog
- Thermostat T32P

- Manufacturer
- JacksonSystems
- Product
- T32P/Chameleon
- Model
- T32P
- Protocol
- Modbus
- Package
- Temperature control (SU2203)
- Updated
- 2025-07-16
- Driver ID
- 322
Notes
Wall thermostat Driver assumes thermostat is set for 2-point day/night mode (DIP 6 off & DIP 8 on). Optional expression determines day/night mode. Thermostat firmware version 2.16 and higher. Connect: ezeio D0 -> T32P Coms B ezeio D1 -> T32P Coms A ezeio 0V -> T32P Coms T
Registers 11
| # | Name | Unit | Description |
|---|---|---|---|
| 1 | Call | Relay closures | |
| 2 | Outside Temp | Optional external temp sensor (read only) | |
| 3 | Room Temp | Internal temp sensor (read only) | |
| 4 | Setpoint | Current set point (read only) | |
| 5 | Fan | Fan mode | |
| 6 | Mode | Thermostat mode | |
| 7 | Day Cool Set Temp | Cooling set point in day mode | |
| 8 | Day Heat Set Temp | Heating set point in day mode | |
| 9 | Night Cool Set Temp | Cooling set point in night mode | |
| 10 | Night Heat Set Temp | Heating set point in night mode | |
| 11 | Day/Night mode | Set day or night mode |