Skip to content
ezeioDocs
  1. Drivers
  2. Driver catalog
  3. RH/Temp sensor

RH/Temp sensor

XY · XY-MD02 · XY-MD02

RH/Temp sensor
Manufacturer
XY
Product
XY-MD02
Model
XY-MD02
Protocol
Modbus
Updated
2025-07-22
Driver ID
325

Notes

Low cost RH/Temp room sensor

Connect:
ezeio D0 -> B-
ezeio D1 -> A+
ezeio 0V -> -
ezeio +V -> +

Default 9600bps, address 1

To change address, write to holding register 257 (0x0101).
To change speed, write to holding register 258 (0x0102)
0=9600, 2=19200

Registers 5

#NameUnitDescription
1Relative Humidity%RH
2Temperature°C
3Dew point°C
4Temperature°F
5Dew point°F