Skip to content
ezeioDocs
  1. Drivers
  2. Driver catalog
  3. CCS WattNode-Advanced

CCS WattNode-Advanced

CCS Continental Control System · WattNode · Advanced

CCS WattNode-Advanced
Manufacturer
CCS Continental Control System
Product
WattNode
Model
Advanced
Protocol
Modbus
Updated
2026-06-23
Driver ID
98

Notes

Three phase electric energy meter. 
120-600VAC L-N. External CTs.
Modbus 'A-' = D0.

Registers 44

#NameUnitDescription
1Total EnergykW h
2Total PowerkW
3Power phase AkW
4Power phase BkW
5Power phase CkW
6Volt average ph-NV
7Volt phase A-NV
8Volt phase B-NV
9Volt phase C-NV
10Current phase AA
11Current phase BA
12Current phase CA
13Power factor average
14Power factor phase A
15Power factor phase B
16Power factor phase C
19Volt average L-LV
20Volt phase A-BV
21Volt phase B-CV
22Volt phase C-AV
23Total Energy NRkW h
24Positive Energy NRkW h
25Negative Energy NRkW h
26Energy phase AkW h
27Energy phase BkW h
28Energy phase CkW h
29Total Reactive EnergykVAR h
30Reactive Energy phase AkVAR h
31Reactive Energy phase BkVAR h
32Reactive Energy phase CkVAR h
33Reactive Power totalkVAR
34Reactive Power phase AkVAR
35Reactive Power phase BkVAR
36Reactive Power phase CkVAR
37Total Apparent EnergykVA h
38Apparent Energy phase AkVA h
39Apparent Energy phase BkVA h
40Apparent Energy phase CkVA h
41Total Apparent PowerkVA
42Apparent Power phase AkVA
43Apparent Power phase BkVA
44Apparent Power phase CkVA
45Reset energy
46FrequencyHz

More from CCS Continental Control System