Generac ATS X

Generac · TX series · TX611

Generac ATS X
Manufacturer
Generac
Product
TX series
Model
TX611
Protocol
Modbus
Updated
2024-09-06
Driver ID
202

Notes

Generat Automatic Transfer Switch TX

Connect:
J13:1 B+ -> ezeio D0
J13:2 A- -> ezeio D1
J13:3 COM -> ezeio GND

Note:
Modbus comms must be "Enabled" via HMI menu. Settings > RS485 > Enable

Device ID# 240 Default

Baud rate 9600 default, 19,200 alternate. 
Use HMI menu to change. Settings > RS485 > Baud > speed

Registers 28

#NameUnitDescription
1ATS Status
2ATS Timers
3Contactor status
4S1 Engine status
5S1 Status Timers
6S2 Engine status
7S2 Status timers
8ATS test status
9Exercise timers
10ATS TVSS statuss
11S1 AB voltageV
12S1 BC voltageV
13S1 AC voltageV
14S2 AB voltageV
15S2 BC voltageV
16S2 AC voltageV
17Current AA
18Current BA
19Current CA
20Current NA
21S1 PowerkW
22S2 PowerkW
23S1 EnergykWh
24S2 EnergykWh
25S1 FreqencyHz
26S2 FreqencyHz
27Temperaure°C
28Humidity%